Investigation of the Effect of Air Change Rate on Contaminant Removal Performance


ÇETİN Y. E., AVCI M., AYDIN O.

JOURNAL OF POLYTECHNIC-POLITEKNIK DERGISI, cilt.24, sa.2, ss.453-459, 2021 (ESCI) identifier identifier

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 24 Sayı: 2
  • Basım Tarihi: 2021
  • Doi Numarası: 10.2339/politeknik.660484
  • Dergi Adı: JOURNAL OF POLYTECHNIC-POLITEKNIK DERGISI
  • Derginin Tarandığı İndeksler: Emerging Sources Citation Index (ESCI), TR DİZİN (ULAKBİM)
  • Sayfa Sayıları: ss.453-459
  • Anahtar Kelimeler: Air change rate (ACH), particle dispersion, contaminant removal, FLOW
  • Karadeniz Teknik Üniversitesi Adresli: Evet

Özet

In this study, the effect of air change rate on particle dispersion is investigated experimentally and numerically for different contaminant source positions. An experimental study is carried out on a reduced scale model for isothermal flow conditions and 0.5 mu m particles are used as contaminants. Particle motions, based on Lagrange approach, are modeled with a computational fluid dynamics (CFD) software ANSYS Fluent. It is found that pollutants outside the main flow region lead to 12 times higher concentration values. In addition, it is determined that the increase in air change rate decreases the concentration of pollutants in this region by 75%.